20 Tendring Hundred Water
Services Limited
| Overall Water Quality supplied by Tendring Hundred
Water Services Limited in 2002 |
- A total of 3,739 tests were carried out on samples taken by
Tendring Hundred Water Services Limited in 2002.
- Of these tests, 99.84% complied with the Regulations.
|
|
| Company
Information |
| Amount of Water Supplied: |
30 Ml/d |
| Consumers Supplied: |
145,000 |
| Areas of Supply: |
Tendring Peninsula of Essex |
| Water Composition: |
20% from rivers and reservoirs |
| |
80% from boreholes and aquifers |
| Treatment Works: |
2 (3 compliance monitoring points) |
| Service Reservoirs: |
8 |
| Km of Mains: |
910 |
| Water Supply Zones: |
4 |
|
|
Water Quality at Treatment Works, in Service
Reservoirs and in Water Supply Zones
To be wholesome, water must comply with the standards for the parameters
set out in the Water Supply (Water Quality) Regulations 1989. In 2002,
the Company carried out a total of 3,739 tests on samples taken at water
treatment works, from service reservoirs and in water supply zones and
of these, 99.84% complied with the relevant water quality standards
set down in the Regulations. A list of the parameters, the relevant
standards and their significance can be found at the beginning of this
section.
Water Quality leaving Treatment works
| |
2002 |
2001 |
2000 |
| Number of water
treatment works |
3 |
3 |
3 |
| COLIFORMS |
|
|
|
| Total number of
tests |
386 |
373 |
631 |
| - |
number containing coliforms |
1 |
0 |
0 |
| - |
% containing coliforms
|
0.26% |
0.00% |
0.00% |
| Treatment works
with coliforms detected |
1 |
0 |
0 |
| - |
% of all works with coliforms
detected |
33.33% |
0.00% |
0.00% |
| FAECAL COLIFORMS |
|
|
|
| Total number of
tests |
386 |
373 |
631 |
| - |
number containing faecal coliforms |
1 |
0 |
0 |
| - |
% containing faecal coliforms |
0.26% |
0.00% |
0.00% |
| Treatment works
with faecal coliforms detected |
1 |
0 |
0 |
| - |
% of all works with faecal
coliforms detected |
33.33% |
0.00% |
0.00% |
Failures of the coliform and faecal coliform standards at one works
in 2002 were considered trivial. Differences over the last three years
in the number of treatment works, and in the number of tests carried
out on samples from treatment works, in which coliforms or faecal coliforms
were detected were not considered significant.
In 2002, the Company were not required to take any regulatory samples
for Cryptosporidium at any of its sites.
Water Quality in Service Reservoirs
| |
2002 |
2001 |
2000 |
| Number of service
reservoirs |
8 |
8 |
8 |
| COLIFORMS |
|
|
|
| Total number of
tests |
410 |
448 |
449 |
| - |
number containing coliforms |
1 |
0 |
0 |
| - |
% containing coliforms
|
0.24% |
0.00% |
0.00% |
| Service reservoirs
with coliforms detected |
1 |
0 |
0 |
| Service reservoirs
with coliforms detected |
0 |
0 |
0 |
| in more than 5%
of tests |
|
|
|
| - |
% of all service reservoirs
with coliforms detected |
0.00% |
0.00% |
0.00% |
| FAECAL COLIFORMS |
|
|
|
| Total number of
tests |
410 |
448 |
449 |
| - |
number containing faecal coliforms |
1 |
0 |
0 |
| - |
% containing faecal coliforms |
0.24% |
0.00% |
0.00% |
| Service reservoirs
with faecal coliforms detected |
1 |
0 |
0 |
| - |
% of all service reservoirs
with faecal coliforms detected |
12.50% |
0.00% |
0.00% |
There were no failures of the coliform standard at any of the service
reservoirs. The detection of faecal coliforms at one service reservoir
was considered trivial. Differences over the last three years in the
number of service reservoirs, and in the number of tests carried out
on samples from service reservoirs, in which coliforms or faecal coliforms
were detected were not considered significant.
Water Quality in Water Supply Zones
The table below shows the data for the key parameters and any other
parameters where there was a failure of the standard. All other parameters
were fully compliant.
| Parameter |
Total
number
of tests |
Tests not meeting
the prescribed
concentration
or value |
Number of
failures
covered by
Undertakings |
Number of zones
not complying with
the standards |
|
|
No |
% |
|
2002 |
2001 |
2000 |
| Coliforms |
377 |
1 |
0.27 |
0 |
0 |
0 |
0 |
| Faecal coliforms |
377 |
0 |
0.00 |
0 |
0 |
0 |
1 |
| Colour |
36 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Turbidity |
54 |
0 |
0.00 |
0 |
0 |
0 |
1 |
| Odour |
36 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Taste |
36 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Hydrogen ion |
41 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Nitrate |
37 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Nitrite |
36 |
0 |
0.00 |
0 |
0 |
0 |
1 |
| Aluminium |
36 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Iron |
118 |
1 |
0.85 |
0 |
1 |
1 |
0 |
| Manganese |
54 |
0 |
0.00 |
0 |
0 |
0 |
1 |
| Lead |
16 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| PAH |
16 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Trihalomethanes |
32 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Total pesticides |
16 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| Other pesticides |
320 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| All others |
509 |
0 |
0.00 |
0 |
0 |
0 |
0 |
| TOTAL |
2,147 |
2 |
0.09% |
0 |
|
|
|
| 4 zones in 2000, 2001 and 2002 |
The New Regulations
In 2002, the Company carried out monitoring for the six new parametric
values set down in the new Water Supply (Water Quality) Regulations
2000. These Regulations come into force on 25 December 2003. The results
are shown in the table below.
| Parameter |
Total number
of tests |
New standard |
Tests not meeting
the new standard |
| Benzene |
25 |
1.0 µg/l |
0 |
| Bromate |
23 |
10.0 µg/l |
1 |
| 1,2 dichloroethane |
24 |
3.0 µg/l |
0 |
| Nitrite (ex-water treatment
works) |
56 |
0.1 mg/l |
0 |
| Clostridium perfringens |
26 |
0/100 ml |
0 |
| Enterococci |
30 |
0/100 ml |
0 |
Compliance data for 2002 has also been analysed against the revised
standards and the results are shown in the following table.
| Parameter |
Total
number
or tests |
Current
Standard |
Number of
tests not
meeting current
standard |
Revised
Standard |
Number of
tests not
meeting revised
standard |
| Antimony |
4 |
10.0 µg/l |
0 |
5.0 µg/l |
0 |
| Arsenic |
4 |
50.0 µg/l |
0 |
10.0 µg/l |
0 |
| Boron |
4 |
2.0 mg/l |
0 |
1.0 mg/l |
0 |
| Copper |
16 |
3.0 mg/l |
0 |
2.0 mg/l |
0 |
| Lead |
16 |
50.0 µg/l |
0 |
25.0 µg/l1 |
0 |
| |
|
|
|
10.0 µg/l2 |
|
| Nickel |
5 |
50.0 µg/l |
0 |
20.0 µg/l |
0 |
| Nitrite (at consumers' taps) |
36 |
0.1 mg/l |
0 |
0.5 mg/l |
0 |
| PAH |
16 |
0.2 µg/l |
0 |
0.1 µg/l |
0 |
| Tetrachloroethene |
16 |
30.0 µg/l |
|
10.0 µg/l
|
0
|
| Trichloroethene |
16 |
10.0 µg/l |
Details of the new and revised standards, and the reasons for the revisions
where applicable, can be found in chapter J "New Regulations and Associated
Programmes of Work".
1 From 25.12.03
2 From 25.12.13
Company Audit and Inspection
The Company was inspected or audited by the Inspectorate or its appointed
consultants on a number of occasions during 2002. Where relevant, report
summaries are available in the 'Business and Technical' section of the
Inspectorate's web site under 'Audit and Inspection'.
| Audit or Inspection |
Date |
| Review of distribution system undertaking |
August 2002 |
| Inspection of one water treatment works
and one service reservoir |
November 2002 |
| Audit of sampling arrangements |
November 2002 |
| Audit of response to selected consumer complaints |
November 2002 |
| Audit trails of five test results |
December 2002 |
| Review of plumbosolvency treatment and control
programmes of work for lead |
December 2002 |
A number of recommendations were made in respect of action required
to avoid the risk of a breach of a regulatory duty. These recommendations
were in relation to the sample audit trails.
Incidents
The Inspectorate regarded none of the events notified during 2002 by
the Company as incidents. For further details on the classification
of incidents, see chapter C "Events affecting Water Quality" in Part
3.
Enforcement Action
No enforcement action was considered for the Company as a result of
the Inspectorate's activities during 2002.
Undertakings and other Improvement Programmes
Water treatment works and service reservoirs
No improvement programmes were due for completion during 2002.
Distribution
Surveys undertaken in connection with the Company's distribution system
undertaking have demonstrated that no mains renovation is justified.
Lead
The Company has a Regulation 41 programme of work to meet the revised
standard for lead set down in the new Water Supply (Water Quality) Regulations
2000, which will come into force on 25 December 2003. Progress with
the delivery of the programme is monitored by the Inspectorate and has
been satisfactory.
|